Owens Corning® SOFTR® Duct Wrap is a blanket of glass fiber insulation factory-laminated to FRK vapor retarder facing. It is used for external insulation of commercial and residential heating, air-conditioning and dual-temperature ducts.
SOFTR® Duct Wrap FRK
Specifications & Literature
Certifications
UL Greenguard Gold
Performance Attributes
Easy Installation
Moisture Management
Thermal Comfort
Technical Information
PROPERTY | TEST METHOD | VALUE | ||
Operating Temperature | ASTM C 411 | up to 250°F (121°C) | ||
Insulation Jacket Temperature Limit | ASTM C 1136 | up to 150°F (66°C) | ||
Jacket Puncture Resistance | ASTM C 1136 | 25 units (0.7 joules) | ||
Water Vapor Permeance | ASTM E 96 | 0.02 perms | ||
Water Vapor Sorption | ASTM C 1104 | < 3% by weight at 120°F (49°C), 95% R.H.
| ||
Fungi Resistance | ASTM C 1338 | Meets requirements | ||
Thermal Conductivity Installed (Compressed) k-Value
| ASTM C 518 |
Type 75
|
Type 100 |
Type 150 |
Surface Burning Characteristics4
| ASTM E 84 | 25
|
4. The surface burning characteristics of these products have been determined in accordance with ASTM E 84. This standard should be used to measure and describe the properties of materials, products or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating.
Applications
- Air Distribution
- Air Distribution > Duct Insulation
- Pipe and Equipment
- Pipe and Equipment > Equipment
- Pipe and Equipment > Equipment > Mechanical Room
- Pipe and Equipment > Process Piping
- Pipe and Equipment > Process Piping > Above Ground Piping
- Pipe and Equipment > Process Piping > Above Ground Piping > Flatwork