Owens Corning® Large Diameter Fiberglas™ Pipe Insulation is molded of heavy density resin bonded inorganic glass fibers. Sections begin at 18" O.D. through 36" O.D. and can be ordered as factory applied SSL® with ASJ Max or as unjacketed No-Wrap.
Large Diameter Fiberglas™ Pipe Insulation
Specifications & Literature
Specifications & Literature
undefined (2)
undefined (2)
undefined (2)
undefined (3)
undefined (2)
undefined (1)
undefined (5)
Certifications
Certifications
Performance Attributes
Performance Attributes
Easy to Install
Mold and Mildew Resistance
Technical Information
Technical Information
Physical Properties
PROPERTY | TEST METHOD | VALUE |
Density(size dependent) | ASTM C302 | 3.5 to 5.5 pcf |
Operating Temperature Range 1 | ASTM C411 | 0°F to 1,000°F(-18°C to 538°C) |
Water Vapor Sorption | ASTM C1104 | Less than 5% by weight |
Corrosion | ASTM C665 | Pass - steel, copper, or aluminum |
Corrosion | ASTM C1617 | Pass - steel |
Jacket Temperature Limitation | ASTM C1136 | -20°F to 150°F (-29°C to 66°C) |
Jacket Permeance | ASTM E96, Proc. A | 0.02 perm |
Burst Strength, min | ASTM D774/D774M | 100 psi |
Composite Surface Burning Characteristics Jacketed 2 | UL 723, ASTM E84 or CAN/ULC-S102 | Flame Spread 25 |
No-Wrap Surface Burning Characteristics 2 | UL 723, ASTM E84 or CAN/ULC-S102 | Flame Spread 0 |
Standards, Codes Compliance
- ASTM C547, Mineral Fiber Pipe Insulation: Type I, Grade A; and Type IV, Grade B
- ASTM C585, Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and Tubing
- ASTM C1136, Flexible Low Permeance Vapor Retarders for Thermal Insulation: Types I, II, III, IV
- ASTM C795, Thermal Insulation for Use in Contact with Austenitic Stainless Steel 3
- Nuclear Regulatory Commission Guide 1.36, Non-Metallic Thermal Insulation 3
- MIL-PRF-22344E, Insulation, Pipe, Thermal, Fibrous Glass
- MIL-DTL-32585, Type I, Form 4, Facing A
- MIL-DTL-24244D (Ships) Insulation Material with Special Corrosion, Chloride, and Fluoride Requirements 3
- US Coast Guard 164.109/70/0 Non-Combustible (No-Wrap only). See No-Wrap FiberglasTM Pipe Insulation Data Sheet for more information: Pub. No. 10022794
- NFPA 90A and 90B
1. With heat-up schedule when operating temperature between 850oF and 1,000oF.
2. The surface burning characteristics of these products have been determined in accordance with UL 723, ASTM E84 or CAN/ULC-S102. Values are reported to the nearest 5 rating.
3. Preproduction qualification testing complete and on file. Chemical analysis of each production lot required for total conformance. Certification needs to be specified at time of order.
Applications
Applications
Related Products
Related Products
Contact Us
Contact Us
Even though we’re a global company, we’re always ready to answer your questions. Call to speak with an Owens Corning representative.