Skip to main content

Owens Corning Fiberglas VaporWick Pipe Insulation is an innovative insulation product designed specifically for below-ambient temperature applications in severe hot/humid operating enviornments.

Specifications & Literature

Certifications

SCS Recycled Content - Average 53%

SCS Recycled Content - Average 53%

Technical Information

Physical Properties

PROPERTYTEST METHODVALUE
Operating Temperature Range32В°F to 220В°F (0В°C to 104В°C)
Jacket PermeanceASTM E96, Desicant method< 0.15 perm
Jacket Temperature LimitationASTM C1136225В°F (107В°C)
Burst Strength, minASTM D774/D774M55 psi
Corrosion ResistanceASTM C665Meets requirements
Fungi Resistance

ASTM C1338

Meets requirements

Composite Surface Burning Characteristics
Flame Spread
Smoke Developed1

ASTM E84, UL 723, and CAN/ULC-S102


<25
<50

STANDARDS CODES COMPLIANCE

  • ASTM C547, Mineral Fiber Pre-Formed Pipe Insulation, Type 12
  • ASTM C795, Thermal Insulation for Use Over austenitic Stainless Steel3
  • ASTM C585, Inner and Outer Diameters of Rigid Thermal Insulation for Pipe and Tubing
  • Nuclear Regulatory Commission Guide 1.36, Non-Metallic Thermal Insulation3
  • NFPA 90A
  • NYC MEA No. 349-02M
1. The surface burning characteristics of these products have been determined in accordance with ASTM E84, UL 723, and CAN/ULC-S102. These standards should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment, which takes into account all of the factors, which are pertinent to an assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating.
2. Exception required for max use temp.
3. Preproduction qualification testing complete and on file. Chemical analysis of each production lot required for total conformance

eBooks & Guides

Contact Us

Even though we’re a global company, we’re always ready to answer your questions. Call to speak with an Owens Corning representative.