Overview
Overview
The Thermafiber® Impasse® No Backer Bar™ Aluminum-Framed Curtain Wall Perimeter Fire Containment System is a patented perimeter fire containment system. CW-D-1014 will serve any typical building situation with an F-rating of up to two hours.
Specifications and Literature
Products In This Solution
Additional Products
Sold Separately
- Concrete Floor Slab
- Curtain Wall Anchors
- Spandrel Glass
- Aluminum Panels
- Stone Panels
Partner Products
- CW-D-1014 Approved Smoke Sealant: Specified Technologies Inc. - SpecSeal AS200 Elastomeric Spray
- CW-D-1014 Approved Smoke Sealant: Specified Technologies Inc. - SpecSeal Fast Tack Firestop Spray
- CW-D-1015 Approved Smoke Sealant: Hilti - CFS-SP WB Firestop Joint Spray
- CW-D-1015 Approved Smoke Sealant: Hilti - CP 672 FC Firestop Joint Spray
- CW-D-1015 Approved Smoke Sealant: Hilti - CFS-SP SIL Firestop Silicone Joint Spray
- CW-D-1016 Approved Smoke Sealant: RectorSeal - MetaCaulk 1200
- CW-D-1016 Approved Smoke Sealant: RectorSeal - MetaCaulk 1500
- CW-D-1016 Approved Smoke Sealant: RectorSeal - Biostop 750
- CW-D-1016 Approved Smoke Sealant: RectorSeal - Biostop 800
- CW-D-1016 Approved Smoke Sealant: RectorSeal - FlameSafe FS3000 Spray
- CW-D-1017 Approved Smoke Sealant: 3M FIRE PROTECTION PRODUCTS - Fire-Dam Spray 200
Performance Attributes
Easy Installation
Fire Containment
ASTM E2307
ASTM E2307
ASTM E2307 measures the ability of perimeter fire barrier systems to maintain a seal and prevent interior fire spread as the exterior wall assembly deflects and deforms during fire exposure. The ASTM E2307 test exposes the joint to fire from the room of fire origin and the exterior wall to fire from both the interior and the exterior as the fire plume exits the room of fire origin through a window opening. ASTM E 2307 determines the period of time that the perimeter fire containment system will limit flame penetration through the opening between the exterior wall assembly and the floor assembly.
International Building Code, Section 715.4 Compliant
International Building Code, Section 715.4 Compliant
The 2015 International Building Code (IBC), Section 715.4, requires approved perimeter fire containment systems at the intersection of the non-rated exterior curtain wall and the fire-resistance-rated floor assemblies. Although local codes may vary, generally fire resistance rated floor/ceilting assemblies are required in construction types I-A, I-B, II-A, III-A and V-A.
NFPA 285 Exempt
NFPA 285 Exempt
NFPA 285 is required in the International Building Code (IBC) in multiple situations. The NFPA 285 test is to determine that combustibles, when exposed to fire on the exterior face of the wall, do not spread flame over the surface or through the core of the otherwise non-combustible wall assembly. This particular assembly is NFPA 285 exempt if built per CW-D-1014 and only includes noncombustible materials.
UL Fire Resistance Directory
UL Fire Resistance Directory
The UL Fire Resistance Directory is a highly recognized document in the fire stopping industry.
Drawings
Construction Details including CAD drawing files for the Thermafiber® Aluminum-Framed Perimeter Fire Containment System are available for download below.
Curtain WallCW-D-1014 Through 1017
Thermafiber® Impasse® No Backer Bar™ System